WSERD-134.446
Electronic air flow monitor for wall mounting.
The WSERD air flow monitor is suitable for monitoring fans, control dampers, humidifiers and electric heating registers in accordance with DIN 57100, Part 420 and for use with DDC systems. The air flow monitor works according to the calorimetric principle. The heat extraction by the air flow is measured and converted into the switching value. The sensor contains a heating element and two temperature sensors. A microcontroller controls the heating and measures the temperature differences. It calculates the air flow velocity from the stored calibration curves and transmits the value serially to the control unit. Here, another microcontroller determines the switching behavior of the two relays from the default values of the setting controllers. Installation is carried out with suitable screws (not included in the scope of delivery) on a level surface and is position-independent.
| Can be read off | No |
|---|---|
| Number of switching stages | 10 |
| Wire break or measurement circuit monitoring | 20 s |
| Rated impulse voltage | 4000 V |
| Operating voltage | 230 VAC, 50 Hz / 24 VAC, 50 Hz / 24 VDC |
| Transistor output | 15…120 s |
| Adjustable tripping value for flow with fluids | 0.2 … 10 m/s |
| Electric connection | screw terminals |
| With explosion protection | No |
| Sensor element | hot film anemometer |
| Bearing temperature | –10 … 75 °C |
| Length of sensor | 165 mm |
| Housing material | plastic |
| Max. Sensor temperature | 90 °C |
| Max. switching voltage | 230 VAC, 50 Hz |
| Max. switching current | 8 A |
| Medium | Air |
| Medium temperature | −20 … 90 °C |
| Probe integrated in the device | No |
| Min. sensor temperature | -20 K |
| With display | No |
| Included with probe | Yes |
| Switching difference, can be adjusted | Yes |
| Switching contact | 2 two-way contacts |
| Potential free switching contact | Yes |
| Protection class | IP65 Gehäuse / IP54 medienseitig |
| Protection class | II, following appropriate mounting |
| Ambient temperature for evaluation electronics | 0 … 50 °C |
| Ambient temp. for evaluation electronics from | 0 °C |
| Degree of contamination | 2 |
| Dimensions (W x H x D) | 136 mm x 110 mm x 69 mm |
Loading specification text...
No related products found.