Frost protection thermostat, 12 m, IP40, hysteresis 1.5 K, STW, indoor setting
The RTKSA frost protection regulators have been specially developed for air or water-side frost protection of hot water heating coils and heat exchangers in ventilation, heating or air conditioning systems. The capillaries are active along their entire length. The device responds when the minimum response length of the capillary (40 cm) reaches the set scale value. In the event of a sensor break, contact 1-2 is permanently open and contact 1-4 is permanently closed. Unlocking is no longer possible. Note: Mounting clamps, thermowells and protective coils are not included in the scope of delivery and must be ordered separately. Air-side application: For frost protection of heating registers, the capillary is clamped in front of the heating register to be protected with mounting clamps. The JZ-05/6M (metal) or JZ-05/6 K (plastic) mounting clamps must be used for this purpose.
| Number of outputs | 2, 2 |
|---|---|
| Number of control ranges | 1 |
| Output signal | switching |
| External setting | No |
| Operation | internal setpoint adjuster |
| Electric connection | Push-in clamp |
| Electronic control | No |
| With explosion protection | No |
| Colour | anthracite |
| Sensor element | capillary tube |
| Function type (systems engineering) | STW, STW |
| Device version | surface-mounted unit |
| Internal setting | Yes |
| Contact interlocking | No |
| Bearing temperature | –30 … 80 °C |
| Capillary length | 12 m |
| Max. air humidity (non-condensing) | 95 % r.H. |
| Sensor material | Cu |
| Max. Sensor temperature | 120 °C |
| Max. switching voltage | 230 VAC, 50/60 Hz / 230 VDC |
| Max. switching current | 16 (2,5) A, 0,25 A |
| Min. switching voltage | 24 VAC, 50 Hz / 24 VDC |
| Min. switching current | at 24 V (AC/DC) min. 100 mA |
| Mounting/attachment | |
| Control range | -10 … 15 °C, -10 … 15 °C |
| Heating control function | Yes |
| Cooling control function | Yes |
| Switching differential | Heating/cooling: 1,5 K |
| Switching difference, can be adjusted | No |
| Switching element | |
| Switching contact | two-way contact |
| Potential free switching contact | Yes |
| Protection class | IP40 |
| Protection class | I |
| Safety and EMC | in accordance with DIN EN 60730 |
| Scale | Degree Celsius |
| Dimensions (W x H x D) | 53 mm x 146,8 mm x 62,9 mm |