Back to Air conditioning

KTRRU-052.245#00

Room thermostat for chilled ceilings, flush-mounted, 24 VAC/VDC, switch Off/Comfort/ECO

Electronic flush-mounted climate controller for heating/cooling control in 2- and 4-pipe systems for hotel, residential and commercial premises. In conjunction with the corresponding cover set, suitable for all standard switch ranges. Matching cover set no. JZ-007.xxx Up to 5 valve actuators (24V~, normally closed) can be controlled per output. The switch can be used to select between the operating modes Off/Comfort/ECO. Particularly suitable for cooling ceiling control due to the option of dew point monitoring. To compensate for the inertia of controlled systems with cooling ceilings, the device has a temperature sensor input for connecting an external radiation sensor (optional). The factory-set “zero point” of approx. 21 °C can be adjusted by ±5 K in the device. The setpoint temperature can be adjusted by ±3 K around the set zero point using the adjustment knob. The external sensor can also be designed as a room sensor (optional) as an official variant, where the controller should be inaccessible to unauthorized persons. An internal potentiometer can be used to select the use of the internal or external sensor or the use of both sensors with an adjustable weighting. Contact inputs for ECO function and OFF (frost protection).


SKU: UA210401-en Categories: , ,
Number of outputs2, 2
Number of outputs, heating1
Number of outputs, cooling1
Actual temperature displayNo
Temperature controller versionclimate controller
External settingYes
Operationrotary knob and switches
Operating voltage24 VAC ±8 %, 50 Hz / 24 VDC ±20 %, 24 VAC, 50 Hz / 24 VDC
Design
DisplayNo
ECO function (reduction)Yes
Electric connectionscrew terminals
Electronic controlYes
Energy efficiency classI
Colouranthracite
Sensor elementNTC internal, optional NTC external
Bearing temperature–20 … 70 °C
Max. air humidity (non-condensing)95 % r.H.
Housing materialplastic PC
Max. switching voltage24 VAC, 50 Hz / 24 VDC
Max. switching current1 (1) A
Mechanical range reductionYes
Min. switching voltage24 VAC, 50 Hz / 24 VDC
With receiverNo
Mounting/attachmentflush mounting (deep socket recommended)
Neutral zone2 K
Surface finishmatt or gloss (see cover set)
Control range13 … 29 °C, 13 … 29 °C
Heating control function
Cooling control function
Control behaviour2-point
Switching differentialHeating/cooling: 1 K
Switching difference, can be adjustedNo
Switching element
Switch Off/Comfort/ECOYes
On/Off switchYes
Heating/cooling switchNo
Additional heating switchNo
Switch/lamp night-time reductionNo
Switching contact2 normally open contacts
Potential free switching contactNo
Switching power24 W
Protection classIP30
Protection classIII
Sensor externalNo
Safety and EMCin accordance with DIN EN 60730
ScaleRelative scale
Ambient temperature0 … 40 °C
Type of wiringother
Degree of contamination2
Assemblybasic device
Dimensions (W x H x D)71 mm x 71 mm x 49 mm