Back to System technology

JDL-116 A

Differential pressure switch, 250…5000 Pa, external setting

Differential pressure switch for monitoring overpressure, differential pressure or negative pressure of air and non-flammable, non-aggressive gases. Can be used as a fume cupboard or fan monitor or flow monitor to protect electrical heating registers, as a filter monitor, low air pressure protection or limit value controller. Note: Once the differential pressure switch has switched a voltage > 24 V and a current > 0.1 A, the gold coating on the contacts is burnt off. After this, the differential pressure switch can only be operated with this or a higher power. Note: The JZ-06/1 hose set is not included in the scope of delivery and must be ordered separately.

Supplied with attached mounting bracket JZ-10.


Number of outputs2, 2
Number of control ranges1
Output signalswitching
External settingYes
Operation
Pressure connection6.2 mm
Electric connectionscrew terminals
Electronic versionNo
With explosion protectionNo
Colour
Sensor element
Function type (systems engineering)controller
Internal settingNo
Bearing temperature–15 … 80 °C
Max. air humidity (non-condensing)95 % r.H.
Housing material
Max. Pressure30000 Pa
Max. switching voltage230 VAC, 50 Hz / 24 VDC
Max. switching current5 (1) A (230 VAC), 1 A (24 VDC), 0,2 A (30 VDC)
MediumAir, not aggressive
Medium temperature−15 … 80 °C
Min. switching voltage12 VAC, 50 Hz / 12 VDC
Min. switching current1 mA
Mounting/attachment
Surface finishmatt, matt
Pressure control range250 … 5000 Pa
Control function, overpressure or underpressureYes
Switching differential150 … 60 Pa
Switching element
Switching contacttwo-way contact
Potential free switching contactYes
Protection class
Protection classII, following appropriate mounting
Safety and EMCin accordance with DIN EN 60730
Ambient temperature−15 … 80 °C
Degree of contamination2