TPS 1
Dew point sensor for cooling ceilings/mats, 10 m cable
This dew point sensor was specially developed in conjunction with an alre dew point monitor (e.g. WFRRN) or chilled ceiling controller (e.g. KTRRB, KTRRU, KTRRUu, KTRVB, KTFRx) to detect and report the dew point. When installed correctly, it prevents condensation dripping from the cooled parts of the cooling circuit.
Application: Drywall cooling ceiling (plasterboard) with attached capillary tube mat, metal cooling ceiling with integrated capillary tube system. Installation/fastening is carried out using clips on the cooling ceiling capillary tube. Sensor cable can be extended up to 50 m with 2 x 0.5 mm².
| Version of sensor | humidity sensor |
|---|---|
| With explosion protection | No |
| Bearing temperature | –20 … 70 °C |
| Length of supply line | 10 m |
| Measurement of dew point | Yes |
| With mounting material | Yes |
| With supply line | Yes |
| Mounting/attachment | to the cooling ceiling capillary pipe |
| Protection class | IP30 |
| Assembly | sensor, 2 clips for cooling pad |
| Dimensions (W x H x D) | 70 mm x 21,5 mm x 36 mm |
Loading specification text...
No related products found.