Back to Air conditioning

KTRTB-211.108/03

Room thermostat, heating/cooling, surface-mounted, super-flat, 230 VAC, noiseless (triac), traffic white

This controller was specially developed for heating/cooling control in 2-pipe systems for hotels, residential and commercial premises and can control up to 5 valve actuators (normally closed). The KTRTB detects the room temperature with an internal sensor and activates the heating or cooling according to the deviation from the setpoint. The use of a triac as a switching element instead of a relay/bimetal means that there is no switching noise during operation. An internal switch can be used to configure the existing contact input as an ECO contact or standby contact. ECO function: If this function is selected, the temperature is reduced by 3 K in heating mode and increased by 3 K in cooling mode. Standby function: If this function is selected, the controller is switched off (frost protection remains active). Surface/wall mounting (4-hole mounting on flush-mounted box).


SKU: MA700302 Categories: , ,
Number of outputs1
Number of outputs, heating1
Number of outputs, cooling1
Number of control ranges1
Actual temperature displayNo
Temperature controller versionclimate controller
Output signalswitching (PWM)
External settingYes
Operationrotary knob
Operating voltage230 VAC, 50 Hz
DesignBerlin 1000
DisplayNo
ECO input (reduction)230 VAC, 50 Hz
ECO function (reduction)Yes
Electric connectionscrew terminals
Electronic controlYes
Colourtraffic white
RAL colour number (similar)9016
Sensor elementNTC internal
Bearing temperature–20 …  °C
Max. air humidity (non-condensing)95 % r.H.
Housing materialplastic ABS
Max. power consumption< 0,8 W
Max. switching voltage230 VAC, 50 Hz
Max. switching current65 mA
Mechanical range reductionYes
MediumAir
Min. switching voltage230 VAC, 50 Hz
With receiverNo
Mounting/attachmentsurface mounting
Surface finishgloss
Proportional rangeapprox. 1 K
Control range5 … 30 °C
Heating control functionYes
Cooling control functionYes
Control behaviourswitching PWM
Switching differentialHeating/cooling: 0 K
Switching difference, can be adjustedNo
Switching elementTriac
On/Off switchNo
Heating/cooling switchNo
Additional heating switchNo
Switch/lamp night-time reductionNo
Switching contactNC contact
Potential free switching contactNo
Switching power15 W
Protection classIP30
Protection classII, following appropriate mounting
Sensor externalNo
Safety and EMCin accordance with DIN EN 60730
ScaleDegree Celsius
Ambient temperature0 … 40 °C
Type of wiringother
Degree of contamination2
Assemblycomplete device
Dimensions (W x H x D)78 mm x 78,5 mm x 13,9 mm