Back to Air conditioning

KTRRUu257.456#21/V2

Room thermostat with clock, heating/cooling, flush-mounted, 24 VAC/VDC, alre frame, cover 50 x 50 mm, pure white, glossy

Flush-mounted controller for time-dependent heating/cooling control of 2- and 4-pipe systems in hotels, residential and commercial premises. Can be adapted to almost all surface switch programs thanks to different variants. Up to 5 valve actuators (normally open or closed) can be controlled per output. In 2-pipe operation, the operating mode can be switched via an external contact (change-over), temperature sensor or in the menu. The clock can be used as a master for other controllers for ECO switchover. The energy-saving function (ECO) or frost protection (STANDBY) can be activated via an external contact. Alternatively, the controller inputs can be configured for an external temperature sensor (weighting between internal and external sensor can be set) or a dew point sensor (TPS). A fan (EC fan) can be speed-controlled via a 0 … 10 V interface.


SKU: UA220100 Categories: , ,
Adaptive heating time startYes
Number of outputs3
Number of outputs, heating1
Number of outputs, cooling1
Number of switching programs7
Number of control ranges1
Actual temperature displayYes
Display typeilluminated, graphic display
Temperature controller versionclimate controller
Clock versiondigital
Output signalswitching/continuous, 0 … 10 V
External settingYes
Operationtouch-sensitive buttons
Rated impulse voltage500 V
Operating voltage24 VAC, 50 Hz / 24 VDC, 24 VAC, 50 Hz / 24 VDC
DesignBerlin UP
DisplayYes
ECO output (reduction)24 VAC, 50 Hz / 24 VDC
ECO input (reduction)24 VAC, 50 Hz / 24 VDC
ECO function (reduction)Yes
Electric connectionscrewed plug-in terminals
Energy efficiency classI or IV
Colourpure white
RAL colour number (similar)9010
Sensor elementNTC internal, optional NTC external
Power reserve3 Days
Shortest switching time15 min
Bearing temperature–20 … 70 °C
Max. air humidity (non-condensing)95 % r.H.
Housing materialplastic ABS, PC, PMMA
Max. power consumptionapprox, 1 W (2,2 VA)
Max. switching voltage24 VAC, 50 Hz / 24 VDC
Max. switching current3 (0,5) A
MediumAir
Min. switching voltage24 VAC, 50 Hz / 24 VDC
With receiverNo
Mounting/attachmentflush mounting (deep socket recommended)
Neutral zoneeinstellbar
Surface finishgloss
Party functionYes
Control range5 … 40 °C, 5 … 40 °C
Heating control functionYes
Cooling control functionYes
Control behaviour2-point or PI-PWM
Switching differentialHeating/cooling: 1 … 2 K
Switching difference, can be adjustedNo
Switching elementrelay
Heating/cooling switchNo
Switching contact2 normally open contacts
Potential free switching contactNo
Switching power72 W
Protection classIP30
Protection classIII
Sensor externalNo
Safety and EMCin accordance with DIN EN 60730
Clock typeday/week
Ambient temperature0 … 40 °C
Type of wiringother
Degree of contamination2
Weather-dependent controlNo
Dimensions (W x H x D)81 mm x 85 mm x 46 mm

Loading specification text...