RTKSA-101.110
System room thermostat, 0…50 °C, hysteresis 1.3 K, TW, internal setting
The RTKSA plant room thermostats have been specially developed for use in industrial buildings, exhibition halls, air domes and greenhouses. When used as frost protection controllers, the higher tolerances at the end of the scale must be observed.
| Number of outputs | 2, 2 |
|---|---|
| Number of control ranges | 1 |
| Output signal | |
| External setting | No |
| Operation | |
| Electric connection | |
| Electronic control | No |
| With explosion protection | No |
| Colour | |
| Sensor element | |
| Function type (systems engineering) | TW |
| Device version | |
| Internal setting | Yes |
| Bearing temperature | –30 … 80 °C |
| Max. air humidity (non-condensing) | 95 % r.H. |
| Sensor material | V2A |
| Max. Sensor temperature | 57 °C |
| Max. switching voltage | 230 VAC, 50/60 Hz / 230 VDC |
| Max. switching current | 16 (2,5) A, 0,25 A |
| Medium | |
| Min. switching voltage | 24 VAC, 50 Hz / 24 VDC |
| Min. switching current | at 24 V (AC/DC) min. 100 mA |
| Mounting/attachment | |
| Control range | 0 … 50 °C |
| Heating control function | |
| Cooling control function | |
| Switching differential | Heating/cooling: 1,3 K |
| Switching difference, can be adjusted | No |
| Switching element | |
| Switching contact | |
| Potential free switching contact | Yes |
| Protection class | |
| Protection class | I |
| Safety and EMC | in accordance with DIN EN 60730 |
| Scale | Degree Celsius |
| Dimensions (W x H x D) | 85 mm x 118,9 mm x 57,5 mm |
Loading specification text...
No related products found.